1.2 Logic
The Logic tab provides more complex functionality. Up to four groups can be logically compared with
the channel group assignments to determine what the channel output states will be. In the example in
(Figure 2), the Outside Light group is assigned to Channel 11, and the Light Sensor group is a Logic
Group used in conjunction with Channel 11. Since the And logic function is selected, Channel 11 will
switch on only when both the Outside Light and Light Sensor Groups are enabled. If the 'Or logical'
function was selected instead of the 'And', Channel 11 would switch on when either the Outside Light
or the Light Sensor group is enabled (or both).
Figure 2 – Editing the C-Bus
®
L5512RVF 12 Channel Voltage Free Relay, with the Logic tab selected
For a relay unit, logic relationships can be created to simulate switches in series (And logic), or
switches in parallel (Or logic).
For dimmer and analogue output units, logic relationships can be created to ensure the state of the
load will be equal to the maximum level of the associated groups (Max logic). Alternatively, the state
of the load may assume the minimum level of the associated groups (Min logic).